Products Hyper QXchanger™ Dry Cooler CRAH Fan Wall Rear Door Heat Exchanger Heat Path Company Contact Request a Quote

Active rear door

Rear door heat exchanger
for high-density racks.

An active rear door with a microchannel water coil and its own fans. Rack exhaust goes through the coil and into water before it reaches the room. Built to the OCP Open Rack V3 and ACS Door Heat Exchanger specifications.

Rack
OCP ORV3, 600 mm
Door
Pivoting carriage
Power
ORV3 busbar
H100 rear door

How it works

High-density racks
in an air-cooled hall.

Door fans pull the rack's hot exhaust through a water coil. The heat leaves in the facility water loop, and cooled air goes back into the room.

01

Rack exhaust

Hot air leaves the servers into the rear door.

02

Coil + fans

Door fans move it through a microchannel coil; the heat goes into water.

03

Back to the room

Cooled air returns to the room; the water carries the heat to the plant.

The family

Five models
in two lines.

The model number is the capacity class in kW at the OCP ACS Door Heat Exchanger rating point: 16 °C water in, 45 °C air in, 30 °C air out, at sea level.

S35
Standard

S35

35 kW class

S45
Standard

S45

45 kW class

S60
Standard

S60

60 kW class

H80
High-Capacity

H80

80 kW class

H100
High-Capacity

H100

100 kW class

High-Capacity rear door with one fan leaf removed, showing the coil behind

Inside the door

Fans on the rear face.
Coil behind them.

The door swings as one carriage. Its rear face is split into two fan leaves in front of the coil; open a leaf and the coil and plenum are behind it.

Standard-line rear door general arrangement: elevation from the hot aisle and plan view with door swing

General arrangement, Standard line: 600 mm wide on the ORV3 rack, door swing shown in plan. Dimensions in mm.

Design

Design.

Pivoting carriage

One door carriage on a 600 mm ORV3 rack, with a split rear face of two fan leaves.

Microchannel coil

Danfoss microchannel heat exchanger in every model.

Rack-busbar power

DC power taken from the ORV3 busbar. No separate AC feed to the door.

N+1 fans

Designed to hold rated capacity with one fan out of service, with a backdraft baffle at each fan position.

Valve on load

Water flow follows the rack's heat load, with room dew point received digitally.

Two lines, one platform

Standard (S35, S45, S60) and High-Capacity (H80, H100) share the same door architecture.

Controls

Controls.

Door controls are designed for building and data-center management systems, with the protocols an ORV3 deployment expects.

Modbus RTU / TCPBACnetSNMP v2 / v3RedfishHTTP

Talk to QX Dynamics.