Computer room air handlers

CRAH
downflow and upflow.

Chilled-water air handlers for the data hall, in a downflow configuration for raised floors and an upflow configuration for slab floors and overhead supply.

Downflow
125 and 400 kW classes
Fans
EC, airfoil
Controls
BACnet IP
Downflow CRAH

Configurations

Downflow or upflow.

Downflow CRAH

Downflow CRAH

Takes return air in at the top and discharges down into the raised-floor plenum. A vertical arrangement that keeps the footprint on the gallery floor small.

  • ◆Raised-floor data halls with under-floor supply
  • ◆EC fans on a pull-out fan track for removal
  • ◆Optional variable-height plenum
coil EC fans return air supply airto duct or open ceiling slab floor

Upflow CRAH

Top-discharge configuration for overhead ducts or open-ceiling supply. Suits slab-floor data halls where there is no plenum below.

  • ◆Slab-floor halls, overhead duct or open ceiling
  • ◆Variable-speed EC fans
  • ◆Same casing, coil and controls platform as the downflow line

Downflow performance

125 and 400 kW
classes.

Two downflow frames. Each is rated below at a hot-aisle return: gross total coil capacity at the conditions shown.

Downflow CRAH, 3-fan frame
3-fan frame

QXV045C

125 kW class · rated 146.4 kW gross

Airflow20,000 CFM
Entering air98.0 °F DB / 73.0 °F WB
Chilled water70 °F in / 84 °F out, 71.4 gpm
Net of fan heat141.2 kW
Fans3 x EC airfoil, N-1 at 100% airflow
H x W x L95 x 125.2 x 48.9 in
Shipping weight4,805 lb
Electrical480 V / 3 ph / 60 Hz
Downflow CRAH, 5-fan frame
5-fan frame

QXV110C

400 kW class · rated 445.2 kW gross

Airflow60,075 CFM
Entering air102.0 °F DB / 71.5 °F WB
Chilled water70 °F in / 84 °F out, 216.8 gpm
Net of fan heat422.7 kW
Fans5 x EC airfoil, N-1 at 100% airflow
H x W x L192 x 155.8 x 78.1 in, incl. 78 in filter plenum
Shipping weight6,526 lb
Electrical480 V / 3 ph / 60 Hz

Both at 0.20 in external static, 1,030 ft site altitude.

Standard features

Standard features.

Included in the base unit.

Automatic transfer switch

Dual interlocked contactors and dual through-the-door fused disconnects.

Control power ride-through

UPS or power buffer keeps the controls alive through a transfer.

EC fans with airflow feedback

Per-fan airflow reported through the EC fan electronics.

Leak detection + condensate

Rope leak detection and a dual-float condensate pump.

Smoke shutdown

Return-air smoke detector with fan shutdown.

Chilled-water valve

Two-way modulating chilled-water valve.

Construction

Construction.

Casing18 ga G90 galvanized outer panel, black powder coat; 24 ga galvanized liner
Insulation2 in R-8 fiberglass
BaseFormed-channel base
CoilCopper tube, aluminum fin, copper header, galvanized casing
FansAirfoil EC fans, axial discharge
Electrical480 V / 3 ph / 60 Hz, dual fused disconnects, ATS
Controller10 in touch-screen controller, stand-alone or networked

Controls

BACnet IP standard.
Modbus by gateway.

BACnet IP by default. A Modbus gateway joins the unit to a Modbus network, with a published point map.

BACnet IP

Default

Modbus

Via gateway

Talk to QX Dynamics.